Manage an E. coli detection at the Numurkah reservoir
You are the acting incident controller in the Control Centre and Water Quality team.
What has happened
The laboratory has phoned through a presumptive E. coli detection of 3 per 100 millilitres on yesterday's verification sample at reservoir R-19 outlet in Numurkah, which serves about 4,800 people including a hospital, two schools and an aged care home. The free chlorine residual at the same site was 0.22 milligrams per litre, at the alert level. R-19 was the subject of a low residual incident in August and booster dosing was commissioned. The Control Centre and Water Quality Manager is running the event as a full exercise and is playing the health regulator and the Managing Director. You must work the procedure as if the event were real, from first notification through to the clearance plan and the incident report.
Deliverables
- Incident register entry with level and justification
- Resampling plan and register entries
- Health regulator notification
- Draft boil water advisory and critical customer briefing
- Completed Water Quality Incident Report
Documents to use
Systems to use
WHS and Environmental Incident Register
Records injuries, near misses, hazards, chemical releases, sewage spills, water quality incidents and vehicle events with investigation and actions.
Water Quality Sampling Register
Records operational and verification samples, laboratory results and the result status for drinking water, recycled water, effluent and raw water.
Network Work Orders
Tracks every reactive and planned job on the water and sewer networks, plants, storages and channels from dispatch to completion.
Units of competency
Current on training.gov.au for the National Water Training Package as at 10 September 2026.
NWPNET030Identify and respond to water quality problemsNWPGEN032Ensure compliance with water industry standards, guidelines and legislationNWPCCO002Use control centre systems to monitor and control waterNWPTRT002Develop and manage a treatment process monitoring programNWPGEN031Develop an operational planQualifications
NWP40120Certificate IV in Water Industry OperationsNWP50126Diploma of Water Industry OperationsWhat to look for
Evidence guide
Look for the student acting on the presumptive result without waiting for confirmation, setting a level that reflects water already supplied to customers, notifying the regulator within the required time and preparing customer advice that a resident can follow. The cause analysis must use the August incident and the critical control point record. Clearance criteria must require consecutive clear samples with residual. The report must be complete and consistent with the register entries.